Permit: T08CM02034
Permit Details
Apply Date:
06/11/2008
Applicant:
N/A
Description:
REMODEL:INTERIOR OF HOTEL
Contractors:
- D J WILLIAMSON ENTERPRISES INC *C
Permit Reviews
Permit Number - T08CM02034
Permit Status: Expired
Permit Description: REMODEL:INTERIOR OF HOTEL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 06/11/2008 | PLANS OK TO SUBMIT - COMM | 06/12/2008 | COMPLETED |
| 06/13/2008 | COMMERCIAL TI | 09/03/2008 | COMPLETED |
| 09/03/2008 | REVISION - - 1ST | 09/04/2008 | COMPLETED |
| 10/10/2008 | REVISION - - 2ND | 10/21/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08CM02034
Permit Status: Expired
Permit Description: REMODEL:INTERIOR OF HOTEL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/11/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08CM02034
Permite Description: REMODEL:INTERIOR OF HOTEL
Total Outstanding Inspections - 14
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| BUILDING ABOVE CEILING | N/A | Not Inspected | ||
| ELECTRIC - UFER | N/A | Not Inspected | ||
| ELECTRIC - UNDERGROUND | N/A | Not Inspected | ||
| ELECTRIC - TEMPORARY SERVICE | N/A | Not Inspected | ||
| ELECTRIC - SERVICE UPGRADE | N/A | Not Inspected | ||
| 02/06/2009 | ELECTRIC - INTERMEDIATE | N/A | Partial Approval | IVRS - Inspection :* 1. ANY SPLICES OR TERMINATIONS TO BE ACCESSIBLE 2. PROTECT CONDUCTOR FROM SCREWS IN BOXES 314.23 3. ABANDONED VDV CABLING TO BE REMOVED 725.3, 800.3 OK 2ND FLOOR AFTER CORRECTIONS ROOMS 200-242, 274, 276 OK 1ST FLOOR 138-142, 102, 116 OK GROUND SYSTEM AS DISCUSSED |
| 02/06/2009 | ELECTRIC - ABOVE CEILING | N/A | Partial Approval | IVRS - Inspection :* |
| 02/20/2009 | SHEET ROCK NAILING | N/A | Partial Approval | IVRS - Inspection :* PARTY WALLS IN RESTROOMS |
| 12/02/2008 | BUILDING - PROGRESS | N/A | Partial Approval | IVRS - Inspection :* NORTH BUILDING WINDOW FRAME |
| 12/02/2009 | BUILDING - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* NEED TRADE FINALS APPROVED. |
| 12/02/2009 | PLUMBING - FINAL | N/A | Partial Approval | |
| 12/29/2009 | FIRE - FINAL | N/A | Partial Approval | CofO approved for rooms 201 thru 223 and rooms 101 thru 122. |
| 12/30/2009 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1. #200 NOT TO PLANS OR CODE OR READY 2. OUTSIDE CORRIDOR BULBS PAINTED OVER, MAY CREATE FIRE HAZARD FROM HEATING 3. MAINTAIN ALL WORKING CLEARANCES AT ELECTRIC ROOM TO INSPECT 4. PHASE II NOT INSPECTED FOR ROUGH AT THIS TIME 5. FINISH OUTSIDE CORRIDOR COVERS & BULBS FOR FIXTURES ROOMS 201-226 OK AND 101 - 122 OK ROOMS AT ROUGH IN ONLY LOOKED AT 201-226 AND 101-122 |
| 12/30/2009 | MECHANICAL - FINAL | N/A | Partial Approval |
Completed Inspections
Permit Status: Expired
Permit Number: T08CM02034
Permit Description: REMODEL:INTERIOR OF HOTEL
Total Completed Inspections - 9
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/17/2009 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* |
| 12/02/2009 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* 1) PULL AND REPLACE PLUMBING FIXTURES 2) SPOT CHECKED UNITS FOR COMPLIANCE 3) PLUMBING FINAL OK |
| 12/02/2009 | PLUMBING - PROGRESS | RMYERS | Approved | IVRS - Inspection :* |
| 12/02/2009 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* |
| 12/02/2009 | NPPO - FINAL | JLINVILLE | Approved | N/A |
| 12/02/2009 | LANDSCAPE - FINAL | JLINVILLE | Approved | N/A |
| 12/03/2009 | RIGHT OF WAY - FINAL | MOTERO | Approved | |
| 12/30/2009 | MECHANICAL - INTERMEDIATE | MRAMBER | Approved | IVRS - Inspection :* |
| 12/30/2009 | ENGINEERING - FINAL | MRUSSO | Approved |