Permit Details

Status:
Expired
Type:
SINGLE FAMILY ADDITION
Apply Date:
05/22/2008
Applicant:
N/A
Description:
ADDITION: REAR PORCH (SFR)

Permit Reviews

Permit Number - T08CM01678
Permit Status: Expired
Permit Description: ADDITION: REAR PORCH (SFR)
Start Date Submittal Complete Date Status  
05/22/2008 RESIDENTIAL BLDG/ZONING-WALKTHRU 05/22/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T08CM01678
Permit Status: Expired
Permit Description: ADDITION: REAR PORCH (SFR)
Total Outstanding Activity Conditions - 1
Date Name
05/22/2008 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T08CM01678
Permite Description: ADDITION: REAR PORCH (SFR)
Total Outstanding Inspections - 6
Last Inspection Date Description Inspector Results Comments
EXT METAL CLIPS/EXT SHEATHING N/A Not Inspected
SHEET ROCK NAILING N/A Not Inspected
BUILDING - FINAL N/A Not Inspected
ELECTRIC - FINAL N/A Not Inspected
08/06/2008 STUCCO MESH N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UNABLE TO LOCATE ELECTRICAL
2) PLAN TO SHOW COLUMN FIXTURES AND CEILING FANS
3) STUCCO MESH STUCCOED PRIOR TO INSPECTION
08/15/2008 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROBLEM: FROM LAST INSPECTION, DENIED BECAUSE OF ELECTRIC PLAN NOT POSTED. I LOOKED THRU YOUR PAPERWORK AND COULD NOT FIND YOUR ELECTRICAL PLAN. YOU NEED TO HAVE ONE. UNDERGROUND ELECTRIC TO BE 18" BELOW GRADE DIG INSPECTION HOLE HALF WAY FROM SERVICE PANEL TO COL. WHERE IT ENTERS THE FRAME. SCHEDULE 80 CONDUIT REQUIRED ABOVE GRADE AT SERVICE PANEL STUCCO LATH WAS NOT INSPECTED. YOU WILL NEED A STUCCO CARD FROM YOUR CONTRACTOR

Completed Inspections

Permit Status: Expired
Permit Number: T08CM01678
Permit Description: ADDITION: REAR PORCH (SFR)
Total Completed Inspections - 4
Date Description Inspector Results Comments
05/29/2008 EXCAVATION/LAYOUT REBAR & ZON RFREIDIN Approved IVRS - Inspection :*
OK TO POUR

1. NOTE: FOOTINGS FOR COLUMNS TO BE 12" BELOW DIRT GRADE SEE DETAIL, DIG FIGS DEEPER

2. QUESTION
PLAN DOESN'T SHOW SUPPORT FOR (4X2 OR 6X10) AT WEST SIDE OF PORCH?

CIRCLED IN BLUE

IF YOU PLAN ON A POST YOU WILL NEED A FOOTING TYP. TO THE OTHERS
06/26/2008 ROOF NAILING RFREIDIN Approved IVRS - Inspection :*
06/26/2008 FRAMING RFREIDIN Approved IVRS - Inspection :*
06/26/2008 BUILDING PRE-SLAB RFREIDIN Approved IVRS - Inspection :*