Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T08BU02190
Permit Details
Apply Date:
12/23/2008
Applicant:
TRIUMPH BUILDERS SOUTHWEST LLC *C*
Description:
TANKS
Contractors:
- TRIUMPH BUILDERS SOUTHWEST LLC *C*
Permit Reviews
Permit Number - T08BU02190
Permit Status: Expired
Permit Description: TANKS
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
12/22/2008 | TANKS | 12/30/2008 | COMPLETED |
12/23/2008 | TANKS | 12/30/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08BU02190
Permit Status: Expired
Permit Description: TANKS
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
12/23/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08BU02190
Permite Description: TANKS
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
ELECTRIC - FINAL | N/A | Not Inspected |
Completed Inspections
Permit Status: Expired
Permit Number: T08BU02190
Permit Description: TANKS
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2008 | FUEL TANK TIGHTNESS AND HOLE | CFUNKE | Approved | Brine filled Tanks were visualy checked before install. The pea gravel bedding was greater than 12 inches deep. After the tanks were set in the location they were presure tested and then backfilled. |
01/13/2009 | FUEL PIPING INSP. & PRESS TEST | CFUNKE | Approved | Double wall "flex" piping was installed. The primary and secondary walls were tested at the same time. Both passed the pressure and soap test. The vapor recovery is fiberglass piping, it also passed presure and soap testing. All dispenser sumps and tank sumps were filled with water and passed. |
02/12/2009 | FUEL TANK FINAL 791-4502 | BCORRALE | Approved | Approved 2/6 |