Permit: T08BU01702
Permit Details
Apply Date:
09/19/2008
Applicant:
ROADRUNNER FIRE* C
Description:
KITCHEN EXHAUST HOOD FIRE EXTINGUISHING SYSTEM
Contractors:
- ROADRUNNER FIRE* C
Permit Reviews
Permit Number - T08BU01702
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING
SYSTEM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/19/2008 | OTHER | 09/22/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08BU01702
Permit Status: Expired
Permit Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING
SYSTEM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/19/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T08BU01702
Permite Description: KITCHEN EXHAUST HOOD FIRE EXTINGUISHING
SYSTEM
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| FIRE - KITCHEN EXH HOOD FINAL | N/A | Not Inspected | ||
| 10/06/2008 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* 1. INTERLOCK BOTH EXHAUST FANS, MAKE SURE M.U.A IS TIED IN ALSO 2. SEAL ALL HOLES IN HOOD 3. PROVIDE HINGE ASSEMBLY ON EXHAUST FANS TO ALLOW ACCESS FOR CLEANING 4. REPLACE BROKEN CONDUIT TO EXHAUST FANS 5. PROVIDE PROPER GREASE RECEPTACLE ON ROOF OK TO PROCEED WITH FIRE SUPPRESSION SYSTEM |