Permit: T07OT02739
Permit Details
Apply Date:
12/05/2007
Applicant:
GILA SIGN CENTERS INC
Description:
14126
Contractors:
- GILA SIGN CENTERS INC
Outstanding Inspections
Permit Status: Closed
Permit Number: T07OT02739
Permite Description: 14126
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2008 | SIGN SHOP | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. A MARKING LABEL IS NEEDED 2. EQUIPMENT NOT LISTED FOR WET LOCATION - CABLE & POWER SUPPLY 3. REVISE PLANS FOR LED 4. SWITCH TO BE AS PER 600.6 5. BOND LETTERS 600.7 |
| 01/24/2008 | SIGN ELECTRIC | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
Completed Inspections
Permit Status: Closed
Permit Number: T07OT02739
Permit Description: 14126
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2007 | SIGN SITE REVIEW | JSONKIN | Approved | NEED TO PERMIT RICE BOWL LOGO ON WEST ELEVATION OR REMOVE IT. |
| 01/24/2008 | SIGN INSPECTION | JSONKIN | Approved |