Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
MULTI FAMILY OTHER
Address:
3817 E LEE ST #C
Address NEW:
3817 E LEE ST #C
Apply Date:
12/11/2007
Applicant:
JOBS MECHANICAL ,
Description:
REPLACE:A/C & HEAT
Contractors:
  • JOBS MECHANICAL ,

Outstanding Activity Conditions

Permit Number - T07ME00809
Permit Status: Final
Permit Description: REPLACE:A/C & HEAT
Total Outstanding Activity Conditions - 1
Date Name
12/11/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T07ME00809
Permit Description: REPLACE:A/C & HEAT
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/12/2007 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :
See detailed listing on site.| 999*
- CONDENSATE CANNOT TERMINATE INTO A SEWER VENT.
- PAINT EXPOSED PVC W/LATEX PAINT
- PROVIDE MIN. R8 DUCT LINER IN EXPOSED DUCT ON ROOF
- SEAL ALL SPOT WELD HOLES ON DUCT
- PROVIDE A GFI SERVICE RECEPTACLE ON THE ROOF WITH A WATERPROOF BUBBLE TYPE COVER.
- PROVIDE PERMITS FOR ALL AC UNITS ON THIS PROPERTY
06/12/2008 PERMIT FINALED BFLORES Approved
06/12/2008 MECHANICAL - INTERMEDIATE WNORTH Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW