Permit: T07ME00747
Permit Details
Apply Date:
11/05/2007
Applicant:
PUEBLO HEATING & COOLING INC *C
Description:
REPLACE: FURNACE (APA)
Contractors:
- PUEBLO HEATING & COOLING INC *C
Outstanding Activity Conditions
Permit Number - T07ME00747
Permit Status: Expired
Permit Description: REPLACE: FURNACE (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/05/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07ME00747
Permite Description: REPLACE: FURNACE (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2007 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* DO NOT USE TAPE TO SEAL A METAL TO METAL CONNECTION AT TOP OF FURNACE SLEEVE. USE APPROVED DUCT SEALANT REMOVE ALL OLD ASBESTOS TAPE PRIOR TO APPLYING SEALANT. INSULATE SHEETMETAL SLEEVE WITH MIN. R4.2 INSULATION PROVIDE A SEDIMENT TRAP IN GAS LINE AT FURNACE |