Permit: T07ME00505
Permit Details
Apply Date:
07/11/2007
Applicant:
MORANDO MINI
Description:
VIRGIN INSTALL OF TRANE 4 TON SPLIT AC/GAS ( RYAN 296.7926)
Contractors:
- AMERICAN HOME MAINTENANCE INC *C
Outstanding Activity Conditions
Permit Number - T07ME00505
Permit Status: Expired
Permit Description: VIRGIN INSTALL OF TRANE 4 TON
SPLIT AC/GAS ( RYAN 296.7926)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/11/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07ME00505
Permite Description: VIRGIN INSTALL OF TRANE 4 TON
SPLIT AC/GAS ( RYAN 296.7926)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2007 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* - CONDENSATE TRAP IS BACKWARDS - DISCONNECT IS OVERFUSED 40 AMP IS MAX - LOW VOLTAGE WIRING AT CONDENSOR MUST BE PROTECTED FROM DAMAGE. - ALSO WIRING ON ROOFTOP 15 PSI TEST ON GAS PIPE OK LEFT GAS CARD |