Permit: T07ME00480
Permit Details
Apply Date:
06/29/2007
Applicant:
MORANDO MINI
Description:
VIRGIN INSTALL OF TRANE 5T PAC AC/GAS (WILDERSON 749.5421/ 404- 0812)
Contractors:
- AMERICAN HOME MAINTENANCE INC *C
Outstanding Activity Conditions
Permit Number - T07ME00480
Permit Status: Expired
Permit Description: VIRGIN INSTALL OF TRANE 5T PAC
AC/GAS (WILDERSON 749.5421/ 404-
0812)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/29/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07ME00480
Permite Description: VIRGIN INSTALL OF TRANE 5T PAC
AC/GAS (WILDERSON 749.5421/ 404-
0812)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2007 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE COVERS OVER CANVAS CONNECTORS - VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP. - BLOCK & CLAMP PVC AND GAS LINE - EXTEND DRAIN TO WITHIN 6" OF THE GROUND WITH AN ELBOW & NIPPLE. - SECURE DRAIN PIPE TO HOUSE. - PAINT EXPOSED PVC W/LATEX PAINT - PROVIDE A PERMIT FOR ELEC. UPGRADE |