Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T07EL01874
Permit Details
Apply Date:
10/18/2007
Applicant:
BAKER MICHAEL
Description:
NEW CIRCUIT(T06ZV00655)
Contractors:
- MR ELECTRIC OF TUCSON
Outstanding Activity Conditions
Permit Number - T07EL01874
Permit Status: Final
Permit Description: NEW CIRCUIT(T06ZV00655)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/18/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T07EL01874
Permit Description: NEW CIRCUIT(T06ZV00655)
Total Completed Inspections - 4
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/22/2007 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. USE COMPLETE RACEWAY FROM SERVICE TO RECEPTACLE NO OPEN U.F ON SIDE OF HOUSE (USE THHN IN RACEWAY) 2. GROUND J-BOXES 3. INSTALL ON OWN BREAKER AND IDENTIFY CKT ON PANEL DIRECTORY 4. TIGHTEN ALL SCREWS, FITTINGS, ETC. MAKE SURE ALL IS SECURE TO STRUCTURE 5. PANEL NEEDS BLANKS FOR OPEN BREAKER SPACES |
04/14/2008 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection :* |
04/14/2008 | ELECTRIC - UNDERGROUND | CCLEMENS | Approved | IVRS - Inspection :* |
04/15/2008 | PERMIT FINALED | BFLORES | Approved |