Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
1902 N OLD RANCH RD
Apply Date:
03/20/2007
Applicant:
MEHL SANDRA
Description:
Upgrade existing split buss panel to new 200 amp all in one service panel.
Contractors:
  • MEHL ELECTRIC SERVICE INC,*C

Outstanding Activity Conditions

Permit Number - T07EL00488
Permit Status: Expired
Permit Description: Upgrade existing split buss panel to new 200 amp all in one service panel.
Total Outstanding Activity Conditions - 1
Date Name
03/20/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T07EL00488
Permite Description: Upgrade existing split buss panel to new 200 amp all in one service panel.
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
03/28/2007 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE ENERGIZED PRIOR TO APPROVALS
2. NEED TO INSTALL #10 GROUND WITH #10 30A
WTR. HTR. CKT. NEC 250.122
3. GROUND SINGLE GANG BOX USING #10
NEC 250.122

Documents

File Name Document Type  
None DOCUMENTS VIEW