Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Closed
Type:
SINGLE FAMILY OTHER
Address:
10 E SUSANA ST
Address NEW:
10 E SUSANA ST
Apply Date:
01/10/2007
Applicant:
WOOLLEY CHRISTIAN P
Description:
ELEC RECONNECT

Outstanding Activity Conditions

Permit Number - T07EL00058
Permit Status: Closed
Permit Description: ELEC RECONNECT
Total Outstanding Activity Conditions - 1
Date Name
01/10/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T07EL00058
Permite Description: ELEC RECONNECT
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/11/2007 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE EQUIP. DISCONNECTS DOUBLE LUGGED & 2 ADDED TO MAIN DISCONNECT. ALSO, MAIN DISCONNECT HAS WATER DAMAGE (RUST) DUE TO WEATHER. ELECTRICAL SERVICE NEEDS TO BE UPGRADED.
2. CONDUIT CONNECTOR NOT INSTALLED CORRECTLY FOR SECURITY LTG. ABOVE SERVICE.
3. PERMIT REQUIRED FOR NEW AC UNIT.
4. HOUSE NEEDS TO BE UNLOCKED FOR INSPECTION OR MEET INSPECTOR. BE SURE ALL ELECTRICAL DEVICES ARE INSTALLED, COVERS, SMOKE DETECTORS IN BEDROOMS.

RECALL INSPECTION WHEN ACCESS AVAIL.

Documents

File Name Document Type  
None DOCUMENTS VIEW