Permit: T07CM03199
Permit Details
Status:
Expired
Type:
COMMERCIAL OTHER
Address:
6422 E SPEEDWAY BL #150
Address NEW:
6422 E SPEEDWAY BL #150
Apply Date:
07/31/2007
Applicant:
HOLLYWOOD CO INC
Description:
INSTALL A/C UNIT W/ELECT
Contractors:
- HOLLYWOOD CO INC
Permit Reviews
Permit Number - T07CM03199
Permit Status: Expired
Permit Description: INSTALL A/C UNIT W/ELECT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/31/2007 | OTHER | 01/03/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07CM03199
Permit Status: Expired
Permit Description: INSTALL A/C UNIT W/ELECT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/31/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07CM03199
Permite Description: INSTALL A/C UNIT W/ELECT
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2008 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED ELECTRICIAN PRESENT TO OPEN LIVE EQUIPMENT 2. NEED PLANS 3. WHERE IS DISCONNECTING MEANS FOR LOWER UNIT 4. CORD CANNOT RUN ABOVE CEILING 5. NEED ROOF ACCESS |
| 06/02/2008 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection :* SECURE THE CONDENSOR TO REDWOOD SLEEPERS RECOMMEND USING A CONDENSATE PUMP WITH AN OVERFLOW SENSOR OR RELOCATE PUMP |