Permit: T07CM03080
Permit Details
Apply Date:
07/20/2007
Applicant:
N/A
Description:
REPAIRS:ELECTRIC T06DV00604
Contractors:
- LENNIE S ELECTRIC INC *C
Permit Reviews
Permit Number - T07CM03080
Permit Status: Expired
Permit Description: REPAIRS:ELECTRIC T06DV00604
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/20/2007 | OTHER | 08/02/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07CM03080
Permit Status: Expired
Permit Description: REPAIRS:ELECTRIC T06DV00604
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/20/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T07CM03080
Permite Description: REPAIRS:ELECTRIC T06DV00604
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2007 | ELECTRIC - INTERMEDIATE | N/A | Not ready for Inspection | IVRS - Inspection :* 1. THIS IS A SUB-PANEL NOT MAIN. THIS IS A 2ND STRUCTURE PROVIDE GROUNDING ELECTRODE SYSTEM AND SEPARATE GROUNDS AND NEUTRALS 250.24 2. LABEL BREAKERS 3. WHERE ARE GAS & WATER BONDS? (250.104) |
| 08/14/2007 | ELECTRIC - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* MEET WITH CUSTOMER TO EXPLAIN WORK TO BE DONE |