Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Si_xpire
Type:
COMMERCIAL OTHER
Address:
1999 E AJO WY
Address NEW:
1999 E AJO WY
Apply Date:
05/03/2007
Applicant:
RELIABLE PERMIT MANAGEMENT
Description:
FOUNDATION ONLY FOR CONVIENENCE STORE W/U/G UTILI
Contractors:
  • RIO WEST DEVELOPMENT AND CONSTRU

Permit Reviews

Permit Number - T07CM01860
Permit Status: Si_xpire
Permit Description: FOUNDATION ONLY FOR CONVIENENCE STORE W/U/G UTILI
Start Date Submittal Complete Date Status  
05/03/2007 PLANS OK TO SUBMIT - 3RD PARTY 05/03/2007 COMPLETED Review Details
05/03/2007 3RD PARTY REVIEW-COMMERCIAL 05/29/2007 COMPLETED Review Details
05/29/2007 POST 3RD PARTY REVIEW 06/08/2007 COMPLETED Review Details
06/07/2007 RESUBMITTAL 06/07/2007 ACTIVE Review Details
07/18/2007 3RD PARTY REVIEW-REVISION/OTHER 07/24/2007 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07CM01860
Permit Status: Si_xpire
Permit Description: FOUNDATION ONLY FOR CONVIENENCE STORE W/U/G UTILI
Total Outstanding Activity Conditions - 4
Date Name
05/03/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.
05/29/2007 SPECIAL INSPECTION FOR STRUCTURAL MASONRY IS REQUIRED.
05/29/2007 SPECIAL INSPECTION FOR FOUNDATION/EXCAVATION IS REQUIRED.
11/07/2007 SPECIAL INSPECTION IS REQUIRED FOR NEED WW REVIEW AND APPROVAL. SEE L/H/N

Completed Inspections

Permit Status: Si_xpire
Permit Number: T07CM01860
Permit Description: FOUNDATION ONLY FOR CONVIENENCE STORE W/U/G UTILI
Total Completed Inspections - 13
Date Description Inspector Results Comments
06/20/2007 PLUMBING - ROUGH, SOIL RLEDONNE Approved IVRS - Inspection :*
07/03/2007 ELECTRIC - UFER RMAJUTA Approved IVRS - Inspection :*
#2 COPPER TO REBAR AT ELECT. SERVICE AREA
07/03/2007 PLUMBING - PRE SLAB RLEDONNE Approved IVRS - Inspection :*
07/03/2007 EXCAVATION/LAYOUT REBAR & ZON AALEGRIA Approved IVRS - Inspection :*
07/03/2007 BUILDING PRE-SLAB AALEGRIA Approved IVRS - Inspection :*
11/01/2007 ELECTRIC - UNDERGROUND DSANTACR Approved IVRS - Inspection :*
11/01/2007 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :*
11/09/2007 ENGINEERING - FINAL MAVERY Approved Hold building and site work under permit T07CM01981.
11/13/2007 FIRE - FINAL CSCHULTZ Approved
11/14/2007 PLUMBING - FINAL RLEDONNE Approved IVRS - Inspection :*
11/14/2007 FIRE SPKLR - UG PIPING FLUSH CSCHULTZ Approved Under ground piping was not witness flushed, building was to be sprinkler but they did not do it, according to the builder build is not big enough to sprinkler. The trade off was given to cut the water requirements for the whole project in half if they sprinkler all buildings on property. According to city water piping was not finished and water supply was not met. Builder is putting in new piping to meet water supply demands as on 11-14-2007.
11/14/2007 BUILDING - FINAL GDABBS Approved IVRS - Inspection :*
05/15/2008 PERMIT FINALED LJACKSON Approved