Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T06OT02281
Permit Details
Apply Date:
08/28/2006
Applicant:
KORET
Description:
11756
Contractors:
- GRAHAM S NEON L L C
Outstanding Inspections
Permit Status: Expired
Permit Number: T06OT02281
Permite Description: 11756
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/02/2006 | SIGN SHOP | N/A | Not ready for Inspection | IVRS - Inspection :* 1) A MARKING LABEL IS NEEDED ON SIGN 600.4 2) FLEX ARMOR IS BROKEN 3) A DISCONNECT SWITCH OR LOCK OUT IS NEEDED 600.6 4) BOND METALLIC LETTERS 600.7 5) NEED TO ACCESS CABINET FOR LED POWER SUPPLY 6) SUPPORT FLEX CONDUIT |
11/02/2006 | SIGN ELECTRIC | N/A | Not ready for Inspection | IVRS - Inspection :* |
Completed Inspections
Permit Status: Expired
Permit Number: T06OT02281
Permit Description: 11756
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/12/2006 | SIGN INSPECTION | JYBARRA | Approved | IVRS - Inspection :* |