Permit: T06OT00947
Permit Details
Apply Date:
04/05/2006
Applicant:
TUCSON COMMUNICATIONS LLC
Description:
C OF O: OFFICE
Permit Reviews
Permit Number - T06OT00947
Permit Status: Expired
Permit Description: C OF O: OFFICE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/05/2006 | C OF O | 04/05/2006 | COMPLETED |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06OT00947
Permite Description: C OF O: OFFICE
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| MECHANICAL - FINAL | N/A | Not Inspected | ||
| 04/11/2006 | BUILDING - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED INSULATION KITS ON TRAPS UNDER SINKS IN BOTH RESTROOMS. 2. NEED ADA SIGNAGE AT RESTROOM 3. MUST HAVE FLUSH HANDLE ON TANK ON WIDE SIDE OF TOILET TANK. 4. MUST HAVE ALL OTHER FINALS APPROVED PRIOR TO BUILDING FINAL. |
| 04/11/2006 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. RECEPTACLE TO RIGHT OF ENTRY DOOR HAS REVERSED POLARITY. 2. CHECK BATTERIES FOR ALL EMERGENCY LIGHTING AND MAKE SURE THEY ALL WORK. 3. MAKE SURE PANEL DIRECTORY IS MARKED CORRECTLY. |
Completed Inspections
Permit Status: Expired
Permit Number: T06OT00947
Permit Description: C OF O: OFFICE
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2006 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |