Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
2431 N WALNUT AV
Address NEW:
2431 N WALNUT AV
Apply Date:
01/10/2006
Applicant:
WALT PERKO
Description:
INSTALL HEAT A/C PACK
Contractors:
  • A PLUS AIR CONDITIONING L L C

Permit Reviews

Permit Number - T06ME00017
Permit Status: Expired
Permit Description: INSTALL HEAT A/C PACK
Start Date Submittal Complete Date Status  
01/10/2006 MECHANICAL 01/10/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06ME00017
Permit Status: Expired
Permit Description: INSTALL HEAT A/C PACK
Total Outstanding Activity Conditions - 1
Date Name
01/10/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06ME00017
Permite Description: INSTALL HEAT A/C PACK
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
MECHANICAL - FINAL N/A Not Inspected
01/11/2006 MECHANICAL - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE A CONDENSATE DRAIN TO AN APPROVED LOCATION
ALL EXPOSED SUPPLY DUCT ON ROOF MUST BE INSULATED WITH MIN. R-8 INSULATION - RETURN DUCT W/R-4
BLOCK & CLAMP ELEC. CONDUIT ON ROOF
PROVIDE A DEDICATATED CIRCUIT FOR A/C UNIT
IDENTIFY CIRCUIT BREAKER
ELEC. WIRE TO A/C UNIT NOT LISTED ON LABELED & NO ADEQUATE SIZE. DO NO USE WHITE WIRE FOR LINE VOLTAGE
RETURN AIR CANNOT BE PULLED FROM A BATHROOM
OPENING IN CEILING IS NOT SIZED CORRECTLY
WHERE IS THE FILTER LOCATED?

Documents

File Name Document Type  
None DOCUMENTS VIEW