Permit: T06ME00017
Permit Details
Apply Date:
01/10/2006
Applicant:
WALT PERKO
Description:
INSTALL HEAT A/C PACK
Contractors:
- A PLUS AIR CONDITIONING L L C
Permit Reviews
Permit Number - T06ME00017
Permit Status: Expired
Permit Description: INSTALL HEAT A/C PACK
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/10/2006 | MECHANICAL | 01/10/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06ME00017
Permit Status: Expired
Permit Description: INSTALL HEAT A/C PACK
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/10/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06ME00017
Permite Description: INSTALL HEAT A/C PACK
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| MECHANICAL - FINAL | N/A | Not Inspected | ||
| 01/11/2006 | MECHANICAL - INTERMEDIATE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE A CONDENSATE DRAIN TO AN APPROVED LOCATION ALL EXPOSED SUPPLY DUCT ON ROOF MUST BE INSULATED WITH MIN. R-8 INSULATION - RETURN DUCT W/R-4 BLOCK & CLAMP ELEC. CONDUIT ON ROOF PROVIDE A DEDICATATED CIRCUIT FOR A/C UNIT IDENTIFY CIRCUIT BREAKER ELEC. WIRE TO A/C UNIT NOT LISTED ON LABELED & NO ADEQUATE SIZE. DO NO USE WHITE WIRE FOR LINE VOLTAGE RETURN AIR CANNOT BE PULLED FROM A BATHROOM OPENING IN CEILING IS NOT SIZED CORRECTLY WHERE IS THE FILTER LOCATED? |