Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
702 W KENTUCKY ST
Apply Date:
11/20/2006
Applicant:
ARVIZU PASQUAL B & TERESA A & MORALES
Description:
UPGRADE:ELECTRIC 200AMP

Permit Reviews

Permit Number - T06EL02265
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 200AMP
Start Date Submittal Complete Date Status  
11/20/2006 ELECTRICAL 11/20/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06EL02265
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Activity Conditions - 1
Date Name
11/20/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06EL02265
Permite Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
12/21/2006 ELECTRIC - SERVICE UPGRADE N/A Partial Approval IVRS - Inspection :*
1. SUPPORT RISER CONDUIT BELOW ROOF LINE USE MIN. 1/4" BOLTS.
2. INSTALL PERMANENT ADDRESS LABEL
3. MAST FOR RISER SUPPORT MUST BE LISTED, HOMEMADE OUT OF EMT NOT APPROVED.
4. USE BUBBLE TYPE COVER FOR GFI RECEPT
5. CONDUIT NOT SCREWED INTO HUB PROPERLY NOT THREADED ENOUGH.
6. GROUND RODS MUST BE 6' APART OR MORE

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW