Permit: T06EL02265
Permit Details
Apply Date:
11/20/2006
Applicant:
ARVIZU PASQUAL B & TERESA A & MORALES
Description:
UPGRADE:ELECTRIC 200AMP
Permit Reviews
Permit Number - T06EL02265
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 200AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 11/20/2006 | ELECTRICAL | 11/20/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06EL02265
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/20/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL02265
Permite Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2006 | ELECTRIC - SERVICE UPGRADE | N/A | Partial Approval | IVRS - Inspection :* 1. SUPPORT RISER CONDUIT BELOW ROOF LINE USE MIN. 1/4" BOLTS. 2. INSTALL PERMANENT ADDRESS LABEL 3. MAST FOR RISER SUPPORT MUST BE LISTED, HOMEMADE OUT OF EMT NOT APPROVED. 4. USE BUBBLE TYPE COVER FOR GFI RECEPT 5. CONDUIT NOT SCREWED INTO HUB PROPERLY NOT THREADED ENOUGH. 6. GROUND RODS MUST BE 6' APART OR MORE |