Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
1807 W LESTER ST
Address NEW:
1807 W LESTER ST
Apply Date:
11/02/2006
Applicant:
FELIX FRANK
Description:
UPGRADE:ELECTRIC TO 200 AMP R1 REWIRE

Permit Reviews

Permit Number - T06EL02188
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC TO 200 AMP R1 REWIRE
Start Date Submittal Complete Date Status  
11/02/2006 ELECTRICAL 11/02/2006 COMPLETED Review Details
11/30/2006 ELECTRICAL 11/30/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06EL02188
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC TO 200 AMP R1 REWIRE
Total Outstanding Activity Conditions - 1
Date Name
11/02/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06EL02188
Permite Description: UPGRADE:ELECTRIC TO 200 AMP R1 REWIRE
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
07/24/2007 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. SECURE OVEN IN PLACE
2. NEED DISCONNECTING MEANS FOR HOT WATER HEATER AND A #10 CU EQUIPMENT GROUND
3. INSTALL SWITCH COVER PLATE IN LAUNDRY, DRYER CORD NOT IN CONNECTOR
4. PROVIDE LADDER FOR ROOF INSPECTION
11/16/2006 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TAKE OUT PERMIT FOR NEW INTERIOR WIRING AND OTHER WORK.
2. PROVIDE A LISTED GUY GIT OR STIFF ARMS FOR MAST BRACE.
3. DO A BETTER JOB OF SECURING LOWER HALF OF SERVICE AND GFI TO STRUCTURE.

Completed Inspections

Permit Status: Expired
Permit Number: T06EL02188
Permit Description: UPGRADE:ELECTRIC TO 200 AMP R1 REWIRE
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/22/2006 TEP CLEARANCE - AM BFLORES Approved OK INCR PER C.CLEMENS