Permit: T06EL02166
Permit Details
Apply Date:
10/31/2006
Applicant:
DESERT ELECTRIC C*
Description:
ELEC UPGRADE 200AMPS
Contractors:
- DESERT ELECTRIC C*
Permit Reviews
Permit Number - T06EL02166
Permit Status: Expired
Permit Description: ELEC UPGRADE 200AMPS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/31/2006 | ELECTRICAL | 10/31/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06EL02166
Permit Status: Expired
Permit Description: ELEC UPGRADE 200AMPS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/31/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL02166
Permite Description: ELEC UPGRADE 200AMPS
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2006 | ELECTRIC - SERVICE UPGRADE | N/A | Partial Approval | IVRS - Inspection :* 1. BOND GROUND BUSS TO ENCLOSURE 2. INSTALL ALL STRANDS UNDER TERMINAL LUG 3. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 408.6 4. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT. 5. FINISH POOL EQUIPMENT CONNECTIONS. |
Completed Inspections
Permit Status: Expired
Permit Number: T06EL02166
Permit Description: ELEC UPGRADE 200AMPS
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. HOLLANDER |