Permit: T06EL01758
Permit Details
Apply Date:
08/30/2006
Applicant:
SHAFFER ELECTRIC INC , J W
Description:
UPGRADE:ELECTRIC TO 200 AMP
Contractors:
- SHAFFER ELECTRIC INC , J W
Outstanding Activity Conditions
Permit Number - T06EL01758
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC TO 200 AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/30/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T06EL01758
Permit Description: UPGRADE:ELECTRIC TO 200 AMP
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2006 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* 1. USE APPROVED FITTING WITH LB -- CHASE NIPPLE NOT APPROVED. 2. PLEASE PROVIDE A PERMANENT METAL ADDRESS LABEL. 3. PROTECT CONDUCTORS #4 & LARGER AT FITTING 4. MAINTAIN WORKING CLEARANCES AT SUB-PANEL 110.26 5. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL 250.24 6. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING. 7. CLEAN SURFACE UNDER LUG. 8. SUPPORT A/C CONDUIT 9. PLEASE VERIFY PERMIT FOR NEW A/C |
| 08/31/2006 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* |
| 08/31/2006 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection :* |
| 03/09/2009 | PERMIT FINALED | BFLORES | Approved |