Permit: T06EL01663
Permit Details
Status:
Expired
Type:
MULTI FAMILY OTHER
Address:
953 N DESERT AV #A
Address NEW:
953 N DESERT AV #A
Apply Date:
08/21/2006
Applicant:
N/A
Description:
SERVICE:ELECTRIC REVISED REISER
Architects:
- BRIGHT, RICK LANE
Contractors:
- INFILL CONSTRUCTION L L C
Permit Reviews
Permit Number - T06EL01663
Permit Status: Expired
Permit Description: SERVICE:ELECTRIC REVISED REISER
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/21/2006 | ELECTRICAL | 08/21/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06EL01663
Permit Status: Expired
Permit Description: SERVICE:ELECTRIC REVISED REISER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/21/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL01663
Permite Description: SERVICE:ELECTRIC REVISED REISER
Total Outstanding Inspections - 4
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2006 | ELECTRIC - UNDERGROUND | N/A | Partial Approval | IVRS - Inspection :* 1. CONDUIT TO BE AT DEPTHS PER 300.5 2. FINISH #3 PREVIOUS |
| 10/03/2006 | ELECTRIC - INTERMEDIATE | N/A | Partial Approval | IVRS - Inspection :* |
| 10/03/2006 | ELECTRIC - CABLE DROP | N/A | Partial Approval | IVRS - Inspection :* |
| 11/20/2006 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* ELECTRICAL FINAL APPROVED EXISTING LUGS REPLACED ALL OTHER ITEMS APPROVED. 1. INSTALLATION DOES NOT FOLLOW PLAN - LARGER WIRE & LUGS FILLED IN. 2. MEYERS HUB DOES NOT SET CORRECTLY ON SURFACE. 3. NEW INSTALLED LUGS ARE TOO CLOSE TO CABINET FRAME AND TAPED INSULATION NOT PERMANENT WOULD NEED SOMETHING PERMANENT. |
Completed Inspections
Permit Status: Expired
Permit Number: T06EL01663
Permit Description: SERVICE:ELECTRIC REVISED REISER
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2006 | ELECTRIC - SERVICE UPGRADE | RMAJUTA | Approved | OK SERVICE UPGRADE & OH TO UNDERGROUND |
| 10/10/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED FOR UNITS #A, B, C & D PER R. MAJUTA |