Permit Reviews

Permit Number - T06EL01663
Permit Status: Expired
Permit Description: SERVICE:ELECTRIC REVISED REISER
Start Date Submittal Complete Date Status  
08/21/2006 ELECTRICAL 08/21/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06EL01663
Permit Status: Expired
Permit Description: SERVICE:ELECTRIC REVISED REISER
Total Outstanding Activity Conditions - 1
Date Name
08/21/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06EL01663
Permite Description: SERVICE:ELECTRIC REVISED REISER
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
10/03/2006 ELECTRIC - UNDERGROUND N/A Partial Approval IVRS - Inspection :*
1. CONDUIT TO BE AT DEPTHS PER 300.5
2. FINISH #3 PREVIOUS
10/03/2006 ELECTRIC - INTERMEDIATE N/A Partial Approval IVRS - Inspection :*
10/03/2006 ELECTRIC - CABLE DROP N/A Partial Approval IVRS - Inspection :*
11/20/2006 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
ELECTRICAL FINAL APPROVED
EXISTING LUGS REPLACED ALL OTHER ITEMS APPROVED.

1. INSTALLATION DOES NOT FOLLOW PLAN - LARGER WIRE & LUGS FILLED IN.
2. MEYERS HUB DOES NOT SET CORRECTLY ON SURFACE.
3. NEW INSTALLED LUGS ARE TOO CLOSE TO CABINET FRAME AND TAPED INSULATION NOT PERMANENT WOULD NEED SOMETHING PERMANENT.

Completed Inspections

Permit Status: Expired
Permit Number: T06EL01663
Permit Description: SERVICE:ELECTRIC REVISED REISER
Total Completed Inspections - 2
Date Description Inspector Results Comments
10/09/2006 ELECTRIC - SERVICE UPGRADE RMAJUTA Approved OK SERVICE UPGRADE & OH TO UNDERGROUND
10/10/2006 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED FOR UNITS #A, B, C & D PER R. MAJUTA