Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T06EL01624
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
1908 N SANTA ROSA AV
Address NEW:
1908 N SANTA ROSA AV
Apply Date:
08/16/2006
Applicant:
ESSNER JAMES
Description:
200amp upgrade
Contractors:
- ESSNER ELECTRIC
Outstanding Activity Conditions
Permit Number - T06EL01624
Permit Status: Expired
Permit Description: 200amp upgrade
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/16/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL01624
Permite Description: 200amp upgrade
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2006 | ELECTRIC - FINAL | N/A | Denied | 1) MAKE SURE WATER AND GAS PIPES ARE PROPERLY BONDED 2) INSTALL FLASHING, STRUT CLAMP & BRACE FOR MAST 3) SERVICE NEED MINIMUM 36" FRONT WORKING SPACE, RIGHT NOW A/C UNIT IS BLOCKING THAT AREA 4) SECURE BOND AND GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE |
Completed Inspections
Permit Status: Expired
Permit Number: T06EL01624
Permit Description: 200amp upgrade
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER C. CLEMENS |