Description:
GAS PRESSURE TEST (APA)
Contractors:
  • COMPLETE PLUMBING *T

Outstanding Activity Conditions

Permit Number - T05PL02023
Permit Status: Closed
Permit Description: GAS PRESSURE TEST (APA)
Total Outstanding Activity Conditions - 1
Date Name
12/12/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T05PL02023
Permite Description: GAS PRESSURE TEST (APA)
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
12/13/2005 PLUMBING - FINAL N/A Not ready for Inspection IVRS - Inspection :*
1) PRESSURE TEST OK TO (2) ROOF TOP FURNACES
2) PE IN GROUND OK
3) OK FOR GAS, BUT RECALL FOR FINAL AFTER COMPLETING THE FOLLOWING ITEMS: PROVIDE BONDING OF GAS LINE, PROVIDE WEATHER PROOF SUPPORTS ON ROOF AND SECURE WITH APPROVED CLAMPS AND IF PIPING GAS TO 3RD FURNACE, PRESSURE TEST THAT SECTION OF PIPING
12/30/2005 PLUMBING - GAS PRESSURE TEST N/A Partial Approval IVRS - Inspection :*PRESSURE TEST OK
ROOF WAS BEING COATED, UNABLE TO SEE PIPING TO 3RD FURNACE
PIPING NEEDS TO BE SUPPORTED EVERY CAHNGE OF DIRECTION AND NOT TO EXCEEDS 8'
PIPING MUST BE SECURED WITH CLAMPS
BONDING OF GAS LINE IS REQUIRED
PLEASE REMOVE OLD GAS RISER ON EAST SIDE OF BUILDING
PLEASE RECALL FOR INSPECTION AFTER ROOF WORK IS COMPLETE