Permit: T05PL02023
Permit Details
Apply Date:
12/12/2005
Applicant:
COMPLETE PLUMBING *T
Description:
GAS PRESSURE TEST (APA)
Contractors:
- COMPLETE PLUMBING *T
Outstanding Activity Conditions
Permit Number - T05PL02023
Permit Status: Closed
Permit Description: GAS PRESSURE TEST (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/12/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T05PL02023
Permite Description: GAS PRESSURE TEST (APA)
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2005 | PLUMBING - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* 1) PRESSURE TEST OK TO (2) ROOF TOP FURNACES 2) PE IN GROUND OK 3) OK FOR GAS, BUT RECALL FOR FINAL AFTER COMPLETING THE FOLLOWING ITEMS: PROVIDE BONDING OF GAS LINE, PROVIDE WEATHER PROOF SUPPORTS ON ROOF AND SECURE WITH APPROVED CLAMPS AND IF PIPING GAS TO 3RD FURNACE, PRESSURE TEST THAT SECTION OF PIPING |
| 12/30/2005 | PLUMBING - GAS PRESSURE TEST | N/A | Partial Approval | IVRS - Inspection :*PRESSURE TEST OK ROOF WAS BEING COATED, UNABLE TO SEE PIPING TO 3RD FURNACE PIPING NEEDS TO BE SUPPORTED EVERY CAHNGE OF DIRECTION AND NOT TO EXCEEDS 8' PIPING MUST BE SECURED WITH CLAMPS BONDING OF GAS LINE IS REQUIRED PLEASE REMOVE OLD GAS RISER ON EAST SIDE OF BUILDING PLEASE RECALL FOR INSPECTION AFTER ROOF WORK IS COMPLETE |