Permit: T05PL00673
Permit Details
Apply Date:
04/07/2005
Applicant:
AKITA PLUMBING INC *C
Description:
REPLACE:GAS LINE
Contractors:
- AKITA PLUMBING INC *C
Permit Reviews
Permit Number - T05PL00673
Permit Status: Final
Permit Description: REPLACE:GAS LINE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/07/2005 | PLUMBING | 04/07/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05PL00673
Permit Status: Final
Permit Description: REPLACE:GAS LINE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/07/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T05PL00673
Permit Description: REPLACE:GAS LINE
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/08/2005 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* 1) BLACK IRON PIPE, AND CSST GAS SYSTEMS ARE EACH ENGINEERED SYTEMS-TO COMBINE DIFFERENT SYSTEMS REQUIRES ENGINEERING APPROVAL AND APPROVED PLAN. 2) PROVIDE LISTING FOR CSST TO BE INSTALLED IN AN EXPOSED LOCATION LIKE THE ROOF. 3) CAP OFF ALL OPEN UNUSED GAS LINES. 5) NOTE: PLAN PROVIDED-NO MENTION OF EXPOSED PIPING INTALLATION STD ALLOWS CSST IN EXPOSED LOCATION. SEE PERMIT SPECIALIST NS 6) REINSPECTED 2:15PM 7) OK FOR GAS |
| 04/08/2005 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
| 04/11/2005 | PERMIT FINALED | JKOZUCH | Approved |