Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
08/26/2005
Applicant:
DAWN GERHART
Description:
C OF O OFFICE

Permit Reviews

Permit Number - T05OT02133
Permit Status: Expired
Permit Description: C OF O OFFICE
Start Date Submittal Complete Date Status  
08/26/2005 C OF O 08/29/2005 COMPLETED Review Details

Outstanding Inspections

Permit Status: Expired
Permit Number: T05OT02133
Permite Description: C OF O OFFICE
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
SIGN - FINAL N/A Not Inspected
11/16/2005 BUILDING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*PROVIDE APPROVED PLANS
HAVE ALL OTHER FINALS ( ELECTRIC ) APPROVED
11/16/2005 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CORDS NOT ALLOWED ABOVE CEILING
2) SIGNS TO BE LISTED AND LABELED
3) PLEASE SUPPORT WIRE MOLD CONDUIT ABOVE CEILING
4) PROPERLY SUPPORT M/C CABLES
5) FILL UNUSED OPENINGS IN BOXES WITH APPROVED SEALS ALSO AT PANEL
6) EXPOSED CONDUCTORS UNDER COUNTER
7) PLEASE SUPPORT JUNCTION BOXES
8) MISSING RECEPTACLE COVER
9) USE APPROVED CORD AND CONNECTOR FOR LIGHTING
10) EXTENSION CORDS NOT ALLOWED FOR PERMANENT WIRING
11) MAINTAIN CLEARANCES IN FRONT OF ELECTRICAL PANEL

Completed Inspections

Permit Status: Expired
Permit Number: T05OT02133
Permit Description: C OF O OFFICE
Total Completed Inspections - 3
Date Description Inspector Results Comments
11/16/2005 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :* OK FOR FINAL C OF O
11/16/2005 PLUMBING - FINAL LHANLY Approved IVRS - Inspection :*APPROVED
11/16/2005 FIRE - FINAL LTHOMAS Approved

Documents

File Name Document Type  
None CONSTRPLANS VIEW