Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Closed
Type:
SIGN PERMIT
Apply Date:
02/18/2005
Applicant:
D AND D SIGNS ,
Description:
SIGN:ELECTRIC:8536 BANK OF TUCSON

Outstanding Inspections

Permit Status: Closed
Permit Number: T05OT00375
Permite Description: SIGN:ELECTRIC:8536 BANK OF TUCSON
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
04/21/2005 SIGN SHOP N/A Partial Approval IVRS - Inspection :*
1) WHITE CONDUCTOR NOT AN ALLOWED COLOR 200.7
2) MAINTAIN 1 1/2" SEPERATION FOR GROUNDING CONDUCTORS
3) MARKING LABELS ARE NEEDED 600.4
4) OK LETTERS
04/21/2005 SIGN ELECTRIC N/A Partial Approval IVRS - Inspection :*

Completed Inspections

Permit Status: Closed
Permit Number: T05OT00375
Permit Description: SIGN:ELECTRIC:8536 BANK OF TUCSON
Total Completed Inspections - 2
Date Description Inspector Results Comments
02/22/2005 SIGN SITE REVIEW JSONKIN Approved IVRS - Inspection :*
04/28/2005 SIGN INSPECTION JSONKIN Approved IVRS - Inspection :*