Permit: T05ME00625
Permit Details
Apply Date:
08/26/2005
Applicant:
D AND H AIR CONDITIONING CO,*C
Description:
3 TON GAS PACK (APA)
Contractors:
- D AND H AIR CONDITIONING CO,*C
Outstanding Activity Conditions
Permit Number - T05ME00625
Permit Status: Expired
Permit Description: 3 TON GAS PACK (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/26/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T05ME00625
Permite Description: 3 TON GAS PACK (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2005 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RELOCATE GAS LINE AND ELECTRICAL CONDUIT FROM BLOCKING ACCESS TO THE BLOWER COMPARTMENT. PROVIDE A MINIMUM 10 POUND PRESSURE TEST ON ALL NEW GAS PIPING. OPEN THE SKIRTING ON THE SIDE OF THE MOBILE HOME FOR INSPECTION ON DUCTING NOTE: GAS PIPE MUST MAINTAIN MINIMUM 6" ABOVE THE GROUND |