Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
2265 W GOLDEN HILLS RD
Apply Date:
06/09/2005
Applicant:
MORANDO MINI
Description:
REPLACEMENT OF TRANE XLI19 COND
Contractors:
  • AMERICAN HOME MAINTENANCE INC *C

Outstanding Activity Conditions

Permit Number - T05ME00368
Permit Status: Expired
Permit Description: REPLACEMENT OF TRANE XLI19 COND
Total Outstanding Activity Conditions - 1
Date Name
06/09/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T05ME00368
Permite Description: REPLACEMENT OF TRANE XLI19 COND
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
09/09/2005 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A TRAP ON THE CONDENSATE DRAIN
2) VENT TO BE DOWNSTREAM OF THE TRAP
3) MARK THE UNIT DATA PLATE WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY
4) RELOCATE REFER LINES FROM BLOCKING ACCESS TO FAN COIL
5) RECALL FOR INSPECTION
6) ISOLATE COPPER REFER LINE FROM CONTACTING STEEL STRAP

Documents

File Name Document Type  
None DOCUMENTS VIEW