Permit: T05EL01799
Permit Details
Apply Date:
08/26/2005
Applicant:
TIM KANAVEL
Description:
ELECTRIC RECONNECT
Outstanding Activity Conditions
Permit Number - T05EL01799
Permit Status: Expired
Permit Description: ELECTRIC RECONNECT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/26/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T05EL01799
Permite Description: ELECTRIC RECONNECT
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2005 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. ELECTRIC SERVICE IN NEED OF REPLACEMENT OR REPAIR MAIN DISCONNECT HAS WATER DAMAGE (INDOOR TYPE) AND HAS TRIPLE LUGGING WITH SUB-FEEDER, NOT ALLOWED 2. COOLER RECEPT ON ROOF NEEDS TO BE IN A WEATHER PROOF ENCLOSURE & COVER 3. DRYER OUTLET IN BACK PORCH NEEDS TO BE IN WEATHERPROOF BOX & COVER. 4. WIRING TO SHED NOT TO CODE DISCONNECT & ABANDON OR REWIRE TO CODE MUST HAVE SEPARATE PERMIT. |
| 12/07/2005 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |