Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
5209 S 11TH AV
Address NEW:
5209 S 11TH AV
Apply Date:
07/01/2005
Applicant:
FERNANDEZ THERESA D
Description:
UPDATE ELECTRICAL PANEL

Permit Reviews

Permit Number - T05EL01338
Permit Status: Final
Permit Description: UPDATE ELECTRICAL PANEL
Start Date Submittal Complete Date Status  
07/01/2005 ELECTRICAL 07/01/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05EL01338
Permit Status: Final
Permit Description: UPDATE ELECTRICAL PANEL
Total Outstanding Activity Conditions - 1
Date Name
07/01/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T05EL01338
Permit Description: UPDATE ELECTRICAL PANEL
Total Completed Inspections - 3
Date Description Inspector Results Comments
07/15/2005 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection :* 1) 2 GROUND RODS REQUIRED 6' MIN APART 2) BOND WATER & GAS. 3) CABLES BEHIND PANEL NEED TO BE RUN IN RACEWAY, CANNOT BE EXPOSED. 4) COMPLETE MAKE UP BRANCH CIRCUITS IN PANEL. 5) INSTALL BUSHING TO PROTECT WIRING ENTERING PANEL. 6) SUPPORT RISER CONDUIT WITHIN 3' OF PANEL. RETURN AFTER HOURS INSPECTION PER CUSTOMER REQUEST-NOT RADY 11AM FIRST INSPECTION TIME BY CUSTOMER -PAID $ 108.00 CK 1986. NOTE THAT TEP TIED IN SERVICE DROP & SEALED METER COMPARTMENT PRIOR TO COT INSPECTION. BOOTED METER. INSEPCTOR CALLED IN CLEARANCE TO MAP ROOM 3:30PM
07/15/2005 TEP CLEARANCE - AM JKOZUCH Approved INC
01/12/2006 PERMIT FINALED LJACKSON Approved

Documents

File Name Document Type  
T05EL01338 2025 MASS-UPLOAD.PDF DOCUMENTS VIEW