Permit Reviews
Permit Number - T05EL00486
Permit Status: Final
Permit Description: INSTALL:ELECTRIC PEDESTAL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/11/2005 | ELECTRICAL | 04/15/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05EL00486
Permit Status: Final
Permit Description: INSTALL:ELECTRIC PEDESTAL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/11/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T05EL00486
Permit Description: INSTALL:ELECTRIC PEDESTAL
Total Completed Inspections - 7
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2005 | ELECTRIC - FINAL | MCAPISTR | Approved | IVRS - Inspection :* 1) CORRECTIONS: GROUND ROD CLAMPS SHOULD BE SET AT APPROX. 2" BELOW GRADE 2) FIRST GROUND ROD CLAMPS LOOSE 3) THE 2" RISER PIPE MUST HAVE A LOCK NUT UNDER THE GROUNDING BUSHING. TIGHTEN LOCK NUTS AND INSTALL GROUND WIRE TO BUSHING 4) OK TO CLEAR |
| 05/27/2005 | ELECTRIC - TEMPORARY SERVICE | MCAPISTR | Approved | IVRS - Inspection :* |
| 05/27/2005 | ELECTRIC - CABLE DROP | MCAPISTR | Approved | IVRS - Inspection :* |
| 05/27/2005 | ELECTRIC - INTERMEDIATE | MCAPISTR | Approved | IVRS - Inspection :* |
| 05/27/2005 | ELECTRIC - UNDERGROUND | MCAPISTR | Approved | IVRS - Inspection :* |
| 05/31/2005 | TEP CLEARANCE - AM | HLEYVA | Approved | ECO CLEARED BY CAPISTRAN |
| 12/07/2005 | PERMIT FINALED | LJACKSON | Approved |