Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL ADDITION
Address:
7820 S KOLB RD
Address NEW:
7820 S KOLB RD
Apply Date:
11/07/2005
Applicant:
NELSON-SHIPLEY RANDI
Description:
ADDITION:EQUIPMENT ROOM
Contractors:
  • A P N BUILDERS INC ,

Permit Reviews

Permit Number - T05CM05620
Permit Status: C of o
Permit Description: ADDITION:EQUIPMENT ROOM
Start Date Submittal Complete Date Status  
02/24/2006 3RD PARTY REVIEW-REVISION/OTHER 02/24/2006 COMPLETED Review Details
11/07/2005 PLANS OK TO SUBMIT - 3RD PARTY 11/07/2005 COMPLETED Review Details
11/07/2005 PLANS OK TO SUBMIT - SITE 11/16/2005 COMPLETED Review Details
11/07/2005 3RD PARTY REVIEW-COMMERCIAL 11/14/2005 COMPLETED Review Details
11/14/2005 POST 3RD PARTY REVIEW 11/16/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM05620
Permit Status: C of o
Permit Description: ADDITION:EQUIPMENT ROOM
Total Outstanding Activity Conditions - 1
Date Name
11/07/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T05CM05620
Permit Description: ADDITION:EQUIPMENT ROOM
Total Completed Inspections - 19
Date Description Inspector Results Comments
11/18/2005 BUILDING - FINAL LHANLY Approved IVRS - Inspection :*YOU MUST POST AN ADDRESS VISIBLE FROM KOLB.
12/07/2005 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection :*
1) FINISH CLEANING UP LOOSE RUBBLE IN FOOTING
12/07/2005 ELECTRIC - UFER RSUBA Approved IVRS - Inspection :*
OK BUILDING STAB
02/15/2006 ELECTRIC - INTERMEDIATE RSUBA Approved IVRS - Inspection :*
03/02/2006 FRAMING LHANLY Approved IVRS - Inspection :*
03/06/2006 ELECTRIC - SERVICE UPGRADE RSUBA Approved IVRS - Inspection :*
03/07/2006 TEP CLEARANCE - AM JWEATHER Approved OK TO CLEAR INCR PER R. SUBA
03/09/2006 ELECTRIC - UNDERGROUND RMAJUTA Approved IVRS - Inspection :*
1. LABEL MAIN AS TO WHERE IT FEEDS
2. MAIN DISCONNECT GRID WIRES FROM BUSHINGS TO CAN TO BE #1'S
3. LABEL MCC #2
4. LABEL PNL PP1 MAIN AT MCC #2
5. LABEL PNL AT PP1 OOM
6. OK TO ENERGIZE 600 A DISCONNECT TO MCC #2
7. OK TO ENERGIZE MCC #2
8. OK TO ENERGIZE PANEL PP1, LP1 & HP1 FOR TESTING
03/28/2006 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
OK FOR FINAL C OF O
03/28/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved
03/28/2006 PLUMBING - FINAL RRICH Approved IVRS - Inspection :*
1/2" WATER SUPPLY TO (2) COOLER ONLY OK
03/28/2006 ELECTRIC - FINAL RSUBA Approved IVRS - Inspection :*
03/28/2006 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
03/28/2006 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection :*
03/28/2006 FIRE - FINAL LTHOMAS Approved
03/28/2006 FIRE - HYDRANTS LTHOMAS Approved
03/28/2006 ENGINEERING - FINAL NKALAHAR Approved NO SITE WORK
03/29/2006 RIGHT OF WAY - FINAL PWHIDDON Approved PER EMAIL
09/29/2006 PERMIT FINALED LJACKSON Approved

Documents

File Name Document Type  
STRUCCALCS.TIF DOCUMENTS VIEW
GEOTECHEVAL.TIF DOCUMENTS VIEW
None DOCUMENTS VIEW
T05CM05620.PDF DOCUMENTS VIEW
C OF O_11-01-2006.TIF CERT OF OCC VIEW