Permit Details

Status:
Expired
Type:
SINGLE FAMILY ADDITION
Apply Date:
10/27/2005
Applicant:
MILLETTE SHELIA RAE & JEFFREY A CP/RS
Description:
ADDITION: CONCRETE SLAB W ELECTRICAL AND GAS

Outstanding Activity Conditions

Permit Number - T05CM05472
Permit Status: Expired
Permit Description: ADDITION: CONCRETE SLAB W ELECTRICAL AND GAS
Total Outstanding Activity Conditions - 1
Date Name
10/27/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T05CM05472
Permite Description: ADDITION: CONCRETE SLAB W ELECTRICAL AND GAS
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
EXCAVATION/LAYOUT REBAR & ZON N/A Not Inspected
BUILDING PRE-SLAB N/A Not Inspected
ELECTRIC - FINAL N/A Not Inspected
PLUMBING - FINAL N/A Not Inspected
11/14/2005 PLUMBING - GAS PRESS TEST FNL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL GAS LINES NEED TO BE UNCOVERED COMPLETELY
2) PLAN CALLS FOR 3/4" GAS LINE, 1/2" LINE IS STUBBED THRU CONCRETE SLAB
3) NEED VERIFICATION OF ALL GAS PIPING TO VERIY TYPE OF MATERIALS, CUT COVER, SIZE, ETC...
4) THE PREVIOUS PAPERS HAVE 2010 APPROVED-THAT IS UNDERGROUND ELECTRIC
5) THIS INSPECTION IS FOR UNDERGROUND GAS PIPING

Completed Inspections

Permit Status: Expired
Permit Number: T05CM05472
Permit Description: ADDITION: CONCRETE SLAB W ELECTRICAL AND GAS
Total Completed Inspections - 1
Date Description Inspector Results Comments
10/31/2005 ELECTRIC - UNDERGROUND EDURAZO Approved SHUT OFF REQUIRED ON GAS LINE IN FRONT OF UNION -- PRESSURE TEST REQUIRED ON GAS LINE RECALL

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW