Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Apply Date:
07/26/2005
Applicant:
N/A
Description:
TI: OFFICE
Contractors:
  • DIVISION II CONSTRUCTION COMPANY

Permit Reviews

Permit Number - T05CM03913
Permit Status: C of o
Permit Description: TI: OFFICE
Start Date Submittal Complete Date Status  
07/26/2005 PLANS OK TO SUBMIT - 3RD PARTY 07/26/2005 COMPLETED Review Details
07/26/2005 3RD PARTY REVIEW-COMMERCIAL TI 09/06/2005 COMPLETED Review Details
09/06/2005 POST 3RD PARTY REVIEW 09/08/2005 COMPLETED Review Details
09/08/2005 RESUBMITTAL 09/09/2005 COMPLETED Review Details
10/20/2005 3RD PARTY REVIEW-REVISION/OTHER 10/24/2005 COMPLETED Review Details
12/06/2005 3RD PARTY REVIEW-REVISION/OTHER 12/08/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM03913
Permit Status: C of o
Permit Description: TI: OFFICE
Total Outstanding Activity Conditions - 1
Date Name
07/26/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T05CM03913
Permit Description: TI: OFFICE
Total Completed Inspections - 23
Date Description Inspector Results Comments
10/26/2005 ELECTRIC - INTERMEDIATE DSANTACR Approved IVRS - Inspection :*
11/22/2005 FRAMING AMATHIES Approved IVRS - Inspection :*APPROVED
11/22/2005 FIRE - FINAL LTHOMAS Approved
11/22/2005 FIRE SPKLR - FINAL LTHOMAS Approved
11/22/2005 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
12/06/2005 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :* HOT WATER, RE HEAT COILS, PRESS TEST 10?? PSI
COMB FIRE SMOKE DAMPER INTO RETURN CHASE. TOTALLY INCORRECT.
PLEASE RECALL WHEN SUPT. ON JOB, AND SHT. METAL MA? CAN BE ORGANIZED FOR A MEETING.
ALL COMBUSTIBLES NEED TO BE REMOVED FROM RETUN PLENIUM
12/21/2005 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*
1. YARDWATER IS P.O.C TO EXISTING
2. SEWER IS P.O.C TO EXISTING
3. CORRECTIONS MADE OK - OK TO COVER ALL AREAS
12/21/2005 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
12/21/2005 PLUMBING - SEWER HCS CONNECT RMYERS Approved IVRS - Inspection :*
12/21/2005 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*
12/21/2005 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
12/23/2005 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
12/29/2005 ELECTRIC - ABOVE CEILING CCLEMENS Approved IVRS - Inspection :*STILL HAVE SOME WORK TO DO
LEAVE REMAINDER OF CEILING OPEN
CHECK HOME RUN RACEWAY FILL ( DERATE AS NEEDED)
SUPPORT ALL CEILING FIXTURES AND EXIT LIGHT BOX'S
CHECK NEC 300.22
FOR CEILING WIRING
CHECK BUILDING EMERGENCY SYSTEM CALL WHEN READY FOR FINAL
12/29/2005 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*
12/29/2005 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection :*
12/29/2005 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
01/11/2006 BUILDING - PROGRESS AQUIROZ Approved IVRS - Inspection :*
01/12/2006 MECHANICAL - PROGRESS CWILLIAM Approved
01/12/2006 ELECTRIC - TEMP POWER FOR TEST CCLEMENS Approved
01/12/2006 ELECTRIC - CONSTRUCTION POWER CCLEMENS Approved
01/12/2006 ELECTRIC - FINAL CCLEMENS Approved
01/12/2006 BUILDING - FINAL AQUIROZ Approved
01/12/2006 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*CORRECTIONS MADE OK
PLUMBING FINAL OK
OK FOR C OF O PENDING ANY OTHER INSPECTIONS

Documents

File Name Document Type  
None DOCUMENTS VIEW
C OF O_01-12-2006.TIF CERT OF OCC VIEW