Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
1529 W PRINCE RD
Apply Date:
06/24/2005
Applicant:
PHIL CARHUFF
Description:
TI: SCHOOL

Permit Reviews

Permit Number - T05CM03098
Permit Status: C of o
Permit Description: TI: SCHOOL
Start Date Submittal Complete Date Status  
07/13/2005 COMMERCIAL TI 07/21/2005 COMPLETED Review Details
07/21/2005 3RD PARTY REVIEW-COMMERCIAL TI 08/11/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM03098
Permit Status: C of o
Permit Description: TI: SCHOOL
Total Outstanding Activity Conditions - 1
Date Name
06/24/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T05CM03098
Permit Description: TI: SCHOOL
Total Completed Inspections - 28
Date Description Inspector Results Comments
08/19/2005 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection :*
08/25/2005 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
1) UNDERGROUND OK TO COVER
2) ABS THRU ROOF OK
3) COPPER OK
4) CALL 03075 FOR CLOSET FLANGE INSPECTION
5) OK TO COVER ALL AREAS
08/25/2005 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
08/25/2005 PLUMBING - ROUGH, SOIL RMYERS Approved IVRS - Inspection :*
09/26/2005 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
09/26/2005 FRAMING AQUIROZ Approved IVRS - Inspection :*
10/03/2005 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection :*
10/25/2005 ELECTRIC - ABOVE CEILING RMAJUTA Approved IVRS - Inspection :*
1) MISSING EXIT SIGN BOX FOR ENTRY
2) NO FIXTURE IN CLASSROOM #3, WILL SPRINKLER RISER BE MOVED TO ALLOW FIXTURE TO SET IN, ALSO MUST BE SCREWED TO ?
3) NEC 800-6 FOR COMMUNICATIONS CIRCUITS REQUIRES INSTALLER TO HANG BY STRAPS STAPLES OR HANGERS OR SIMILAR FITTINGS NOT JUST TO BE ? ABOVE CEILING
4) OK TO COVER AREAS NOT AFFECTED-LEAVE OTHER AREAS OPEN
11/14/2005 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection :*
11/14/2005 PLUMBING - PROGRESS RMYERS Approved IVRS - Inspection :*
11/22/2005 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*OK FOR FINAL C OF O
PROVIDE PERMANENT IDENTIFICATION ON A/C UNITS-ADDRESS & UNIT NUMBER
BLDG. INSPECTOR PLEASE VERIFY
11/22/2005 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection :*
1) SERVICE NEEDS TO BE GROUNED
2) REMOVAL OF METAL WATER LINE FEED LEAVES SERVICE UN-GROUNDED
3) TWO GROUND RODS 6' APART WITH #4 OK
11/23/2005 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*YARDWATER OK TO COVER
GAS PRESSURE TEST OK
PLUMBING FINAL OK
OK FOR C OF O PENDING ANY OTHER INSPECTION
CONTRACTOR TO SEAL EXTERIOR WALL PENETRATIONS AND OPEN HOLES IN ROOF
11/23/2005 PLUMBING - GAS PRESSURE TEST RMYERS Approved IVRS - Inspection :*
11/23/2005 PLUMBING - YARD WTR LINE/TEST RMYERS Approved IVRS - Inspection :*
01/06/2006 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
01/06/2006 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
01/06/2006 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved
01/24/2006 BUILDING - PROGRESS AQUIROZ Approved IVRS - Inspection :*
01/24/2006 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
01/25/2006 TEP CLEARANCE - AM JKOZUCH Approved ECO
01/27/2006 FIRE - FINAL LTHOMAS Approved
01/27/2006 FIRE SPKLR - FINAL LTHOMAS Approved
02/03/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved
02/03/2006 BUILDING - FINAL AQUIROZ Approved
02/03/2006 FIRE - ALARM FINAL LTHOMAS Approved
02/06/2006 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
02/07/2006 ENGINEERING - FINAL MRUSSO Approved C OF O FOR ENGINEERING APPROVED