Permit Details

Status:
Expired
Type:
COMMERCIAL ADDITION
Apply Date:
05/25/2005
Applicant:
N/A
Description:
ADDITION: EXHAUST HOOD AND GASLINE STEEL COLUMNS AT HOOD T00VL00045
Contractors:
  • PRECISION STAINLESS MFG ,

Permit Reviews

Permit Number - T05CM02389
Permit Status: Expired
Permit Description: ADDITION: EXHAUST HOOD AND GASLINE STEEL COLUMNS AT HOOD T00VL00045
Start Date Submittal Complete Date Status  
05/25/2005 COMMERCIAL TI 07/20/2005 COMPLETED Review Details
08/30/2005 REVISION - WALK THRU 08/30/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM02389
Permit Status: Expired
Permit Description: ADDITION: EXHAUST HOOD AND GASLINE STEEL COLUMNS AT HOOD T00VL00045
Total Outstanding Activity Conditions - 1
Date Name
05/25/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T05CM02389
Permite Description: ADDITION: EXHAUST HOOD AND GASLINE STEEL COLUMNS AT HOOD T00VL00045
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
08/04/2005 ELECTRIC - ABOVE CEILING N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO PLANS, PERMIT, OR PERSONNEL PRESENT FOR INSPECTION
08/19/2005 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT CONDUIT AND M/C CABLE AND FLEX CONDUIT AS PER CODES
2) USE APPROVED FITTINGS FOR M/C CABLE
3) SUPPORT BOXES
4) WE NEED A DIAGRAM OF THE HOOD AND MAKE-UP AIR INTER LOCK. PLAN TO BE STAMPED APPROVAL
5) PLEASE GROUND ALL JUNCTION BOXES
08/19/2005 FIRE SPKLR - FINAL N/A Denied SUB-CONTRACTOR NOT READY
08/19/2005 FIRE - FINAL N/A Denied SUB-CONTRACTOR NOT READY
10/05/2005 BUILDING - FINAL N/A Partial Approval IVRS - Inspection :* THIS INSPECTION DOES NOT APPLY TO THIS ACTIVITY PER S LONG

Completed Inspections

Permit Status: Expired
Permit Number: T05CM02389
Permit Description: ADDITION: EXHAUST HOOD AND GASLINE STEEL COLUMNS AT HOOD T00VL00045
Total Completed Inspections - 10
Date Description Inspector Results Comments
08/19/2005 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
09/01/2005 PLUMBING - FINAL TRINIVJR Approved IVRS - Inspection :*
1) GAS PRESSURE TEST IS OK
2) GAS SHUT OFF VALVES OK
3) ALL CORRECTIONS HAVE BEEN MADE
09/01/2005 PLUMBING - INTERMEDIATE TRINIVJR Approved
09/01/2005 PLUMBING - GAS PRESSURE TEST TRINIVJR Approved
09/01/2005 PLUMBING - GAS PRESS TEST FNL TRINIVJR Approved
09/06/2005 MECHANICAL - HOODS JMILITEL Approved IVRS - Inspection :*
1) CHECKED FIRE WRAP ON GREASE DUCT
2) NOTE 4800 CFM EVAP COOLER IS NOT EXISTING AS THE PLANS STATE. COOLER AND ALL RELATED DUCT WORK ARE NEW. PLANS WERE APPROVED IN ERROR. MAKE UP AIR MUST BE HEATER. PLEASE HAVE PLANS REVISED SHOWING THE PROPER DESCRIPTION OF WORK
09/28/2005 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
09/28/2005 MECHANICAL - HOOD SYSTEMS JMILITEL Approved
10/05/2005 FRAMING LHANLY Approved IVRS - Inspection :*THIS INSP. DOES NOT SEEM TO APPLY. THERE ARE NO FRAMING DETAILS
10/05/2005 EXCAVATION/LAYOUT REBAR & ZON LHANLY Approved IVRS - Inspection :*THIS INSPECTION DOES NOT SEEM TO APPLY TO THIS PERMIT. NO DETAILS PROVIDED