Permit: T04EL02501
Permit Details
Apply Date:
12/23/2004
Applicant:
DAVID NAGODA
Description:
ELECTRIC:RECONNECT
Outstanding Activity Conditions
Permit Number - T04EL02501
Permit Status: Expired
Permit Description: ELECTRIC:RECONNECT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/23/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04EL02501
Permite Description: ELECTRIC:RECONNECT
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2004 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSED N.M. CABLE NEEDS TO BE REMOVED OR INSTALLED PER NATIONAL ELECTRIC CODE 2) SECURE LOOSE FIXTURES TO J-BOXES 3) PROPERLY JUNCTION ALL EXPOSED CONDUCTORS 4) IMPROPER TAPS AT ELECTRIC SERVICE ( SERVICE NEEDS TO BE UPGRADED ) 5) SERVICE NEEDS GROUNDING ELECTRODE SYSTEM, BOND GAS AND WATER PIPING PER CODE 6) NEED PROPER SIZE OVER CURRENT PROTECTION 7) LB CONDULET FITTING IS MISSING COVER REMOVE OR REPAIR 8) NEED ACCESS TO INTERIOR (BOTH FRONT AND REAR DOORS ARE LOCKED 9:00 AM) |
| 12/27/2004 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |