Permit: T04EL02492
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
2766 E STRATFORD DR
Address NEW:
2766 E STRATFORD DR
Apply Date:
12/21/2004
Applicant:
DIANE DOMINICE
Description:
UPGRADE:ELECTRIC 60AMP TO 100AMP
Permit Reviews
Permit Number - T04EL02492
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/21/2004 | ELECTRICAL | 12/21/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04EL02492
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/21/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04EL02492
Permite Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2004 | ELECTRIC - INTERMEDIATE | N/A | Denied | IVRS - Inspection :1) RISER IS TOO SMALL ( TEP REQUIRES A MIN OF 2" RIGID OR IMC 2) SCH 40 PVC IS NOT ALLOWED EXPOSED WHERE SUBJECT TO PHYSICAL DAMAGE |
| 12/30/2004 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 12/30/2004 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : WOOD USED OUTDOORS FOR SECURING CONDUIT IS NOT AN ACCEPTABLE METHOD OR SUPPORT ( SUGGEST USING UNISTRUT OR EQUAL) |
Completed Inspections
Permit Status: Expired
Permit Number: T04EL02492
Permit Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2004 | ELECTRIC - UNDERGROUND | RSUBA | Approved | IVRS - Inspection : WHERE IS THE GAS BOND TO ELECT. SERVICE |
| 01/04/2005 | TEP CLEARANCE - AM | SLONG | Approved | INC |