Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
12/21/2004
Applicant:
DIANE DOMINICE
Description:
UPGRADE:ELECTRIC 60AMP TO 100AMP

Permit Reviews

Permit Number - T04EL02492
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
Start Date Submittal Complete Date Status  
12/21/2004 ELECTRICAL 12/21/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04EL02492
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
Total Outstanding Activity Conditions - 1
Date Name
12/21/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T04EL02492
Permite Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
12/30/2004 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection :1) RISER IS TOO SMALL ( TEP REQUIRES A MIN OF 2" RIGID OR IMC 2) SCH 40 PVC IS NOT ALLOWED EXPOSED WHERE SUBJECT TO PHYSICAL DAMAGE
12/30/2004 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/30/2004 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
WOOD USED OUTDOORS FOR SECURING CONDUIT IS NOT AN ACCEPTABLE METHOD OR SUPPORT ( SUGGEST USING UNISTRUT OR EQUAL)

Completed Inspections

Permit Status: Expired
Permit Number: T04EL02492
Permit Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
Total Completed Inspections - 2
Date Description Inspector Results Comments
12/30/2004 ELECTRIC - UNDERGROUND RSUBA Approved IVRS - Inspection :
WHERE IS THE GAS BOND TO ELECT. SERVICE
01/04/2005 TEP CLEARANCE - AM SLONG Approved INC

Documents

File Name Document Type  
None DOCUMENTS VIEW