Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T04EL02083
Permit Details
Apply Date:
10/13/2004
Applicant:
ESSNER ELECTRIC
Description:
UPGRADE:ELECTRIC 100-200 AMP
Contractors:
- ESSNER ELECTRIC
Outstanding Activity Conditions
Permit Number - T04EL02083
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC 100-200 AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/13/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T04EL02083
Permit Description: UPGRADE:ELECTRIC 100-200 AMP
Total Completed Inspections - 5
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2004 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :*/1)CHASE NIPPLE NOT APPROVED AS A LISTED FITTING WITH L13? 2)SEAL ENTRANCE ABOVE CURRTON? CARRING PARTS 3)NO CONDUCTORS ALLOWED UP IN METER SECTION AS PER MANUFACTURES LISTING 4)RECPTICAL COVER TO BE WATHER PROOF WHEATHER OR NOT PLUGED IN 408.6 5)SUPPIRT CONDUIT WITHIN 3' OF PANEL 6)PLEASE VERIFY NEW A/C PERMIT 7)PLEASE VERIFY GAS EQUIPMENT BONDING |
| 10/27/2004 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* |
| 10/27/2004 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection :* |
| 04/08/2005 | PERMIT FINALED | MCAPISTR | Approved | |
| 04/08/2005 | TEP CLEARANCE - AM | JKOZUCH | Approved | INC |