Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address NEW:
1304 N CATALINA AV
Apply Date:
10/13/2004
Applicant:
ESSNER ELECTRIC
Description:
UPGRADE:ELECTRIC 100-200 AMP
Contractors:
  • ESSNER ELECTRIC

Outstanding Activity Conditions

Permit Number - T04EL02083
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC 100-200 AMP
Total Outstanding Activity Conditions - 1
Date Name
10/13/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T04EL02083
Permit Description: UPGRADE:ELECTRIC 100-200 AMP
Total Completed Inspections - 5
Date Description Inspector Results Comments
10/27/2004 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*/1)CHASE NIPPLE NOT APPROVED AS A LISTED FITTING WITH L13? 2)SEAL ENTRANCE ABOVE CURRTON? CARRING PARTS 3)NO CONDUCTORS ALLOWED UP IN METER SECTION AS PER MANUFACTURES LISTING 4)RECPTICAL COVER TO BE WATHER PROOF WHEATHER OR NOT PLUGED IN 408.6 5)SUPPIRT CONDUIT WITHIN 3' OF PANEL 6)PLEASE VERIFY NEW A/C PERMIT 7)PLEASE VERIFY GAS EQUIPMENT BONDING
10/27/2004 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
10/27/2004 ELECTRIC - UNDERGROUND RHOLLAND Approved IVRS - Inspection :*
04/08/2005 PERMIT FINALED MCAPISTR Approved
04/08/2005 TEP CLEARANCE - AM JKOZUCH Approved INC