Permit: T04EL02069
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
6409 E CALLE CASTOR
Address NEW:
6409 E CALLE CASTOR
Apply Date:
10/11/2004
Applicant:
PARK JEAN H & HENDERSON KATHLEEN P JT/RS
Description:
UPGRADE:ELECTRIC:60AMP TO 200AMP
Permit Reviews
Permit Number - T04EL02069
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC:60AMP TO 200AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/11/2004 | ELECTRICAL | 10/11/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04EL02069
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC:60AMP TO 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/11/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T04EL02069
Permit Description: UPGRADE:ELECTRIC:60AMP TO 200AMP
Total Completed Inspections - 5
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2004 | ELECTRIC - FINAL | RSUBA | Approved | IVRS - Inspection :install 2nd ground rod (locate min 6' away from each other) BOND GAS PIPE WITH #4 CONDUCTOR AND CONNECT TO NEUTRAL-GROUNDING BUS BAR AT ELECT PANEL RESCHEDULE WHEN COMPLETE |
| 12/13/2004 | ELECTRIC - SERVICE UPGRADE | RSUBA | Approved | IVRS - Inspection :* |
| 12/13/2004 | ELECTRIC - INTERMEDIATE | RSUBA | Approved | IVRS - Inspection :* |
| 12/13/2004 | ELECTRIC - UNDERGROUND | RSUBA | Approved | IVRS - Inspection :* |
| 08/25/2005 | TEP CLEARANCE - AM | FGREER | Approved | INC CLEARED BY SUBA |