Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
214 E 24TH ST
Address NEW:
214 E 24TH ST
Apply Date:
09/08/2004
Applicant:
STEVEN ESCOBEDO
Description:
UPGRADE: ELECTRIC TO 200 AMP

Permit Reviews

Permit Number - T04EL01857
Permit Status: Expired
Permit Description: UPGRADE: ELECTRIC TO 200 AMP
Start Date Submittal Complete Date Status  
09/08/2004 ELECTRICAL 09/08/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04EL01857
Permit Status: Expired
Permit Description: UPGRADE: ELECTRIC TO 200 AMP
Total Outstanding Activity Conditions - 1
Date Name
09/08/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T04EL01857
Permite Description: UPGRADE: ELECTRIC TO 200 AMP
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
10/11/2004 ELECTRIC - UNDERGROUND N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
10/11/2004 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
10/11/2004 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection :The wiring is not complete or does not comply with code.| EXPOSE GROUND RODS
BOND WATER AND GAS PIPING
INSTAL PERMANENT ADDRESS LABEL, MUST BE SCREWED OR RIVETED TO COVER
EMT CONDUIT NOT ALLOWED FOR RISER CONDUIT CK TEP SPECS
ADDITIONAL OR NEW CIRCUITS MUST BE REFLECTED ON PERMIT, ADD TO PERMIT
10/11/2004 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*

Documents

File Name Document Type  
None DOCUMENTS VIEW