Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T04CM03448
Permit Details
Apply Date:
07/27/2004
Applicant:
N/A
Description:
TI:OFFICE
Architects:
- SWAN WAYNE E
Contractors:
- G AND J DEVELOPMENT INC ,
Permit Reviews
Permit Number - T04CM03448
Permit Status: C of o
Permit Description: TI:OFFICE
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
07/27/2004 | COMMERCIAL TI | 07/28/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04CM03448
Permit Status: C of o
Permit Description: TI:OFFICE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
07/27/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T04CM03448
Permit Description: TI:OFFICE
Total Completed Inspections - 12
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2004 | ELECTRIC - INTERMEDIATE | MCAPISTR | Approved | IVRS - Inspection :*/1)ROMEX CONNECTORS ARE NOT TO BE USED ON MC CABLE 2)BENDING RADIUS OF MC MUST BE 5" ON IN 3) TERMINATE ALL MC INTO LIGHT IFIXTURES WITH PROPER CONECTORS TO SECURE CABLE TO BOXES & HOUSINGS |
08/10/2004 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* |
08/11/2004 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
08/12/2004 | RIGHT OF WAY - FINAL | MOTERO | Approved | |
08/12/2004 | ENGINEERING - FINAL | JBRUCKME | Approved | |
08/12/2004 | ELECTRIC - ABOVE CEILING | MCAPISTR | Approved | IVRS - Inspection :* |
08/12/2004 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
08/17/2004 | FIRE SPKLR - FINAL | LTHOMAS | Approved | 1) OK FOR C OF O |
08/17/2004 | FIRE - FINAL | LTHOMAS | Approved | |
08/18/2004 | ELECTRIC - FINAL | MCAPISTR | Approved | IVRS - Inspection :*APPROVED-MARK EMERGENCY LITE CIRCUIT AT PANEL |
08/19/2004 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* |
08/25/2004 | PERMIT FINALED | MCAPISTR | Approved |