Permit: T03PL00462
Permit Details
Apply Date:
03/10/2003
Applicant:
ANA FIGUEROA
Description:
REPLACE:WATER HEATER
Outstanding Activity Conditions
Permit Number - T03PL00462
Permit Status: Expired
Permit Description: REPLACE:WATER HEATER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/10/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T03PL00462
Permite Description: REPLACE:WATER HEATER
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2003 | PLUMBING - FINAL | N/A | Denied | IVRS - Inspection 0999* 1.) REPAIR AGA OR CSA APPROVED GAS VALVE. 2.) WATER HEATER IS NOT RATED FOR OUTDOOR USE. MUST HAVE ENCLOSURE. 3.) FLEX CONNECTOR ON T & P RELIEF DRAIN NOT PERMITTED. 4.) WATER SUPPLY FLEX CONNECTOR KINKED. 5.) USE APPROVED VENT CAP. 6.) REQUIRE PERMIT FOR NEW WATER LINES TO WASHING MACHINE LOCATION PVC REPAIR TEE NOT APPROVED WATER LINE UNION LEAKING. CONNECTION BETWEEN COPPER AND GALVANIZED NOT APPROVED. 7.) SECURE APPLIANCE CONNECTOR AND VENT CONNECTOR. |