Permit: T03OT02113
Permit Details
Apply Date:
12/01/2003
Applicant:
DE LA CRUZ NEON SIGNS ,
Description:
SIGN:6400
Contractors:
- DE LA CRUZ NEON SIGNS ,
Completed Inspections
Permit Status: Final
Permit Number: T03OT02113
Permit Description: SIGN:6400
Total Completed Inspections - 5
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/02/2003 | SIGN SITE REVIEW | JSONKIN | Approved | IVRS - Inspection 0000* |
12/08/2003 | SIGN SHOP | MCAPISTR | Approved | IVRS - Inspection 0000*/ PRE-FAB SIGN TO BE REMOVED AND RE-INSTALLED. |
12/30/2003 | SIGN INSPECTION | DJOHNSTO | Approved | IVRS - Inspection 0620* SIGN ALSO INSTALLED OVER ROOFLINE. NOT AS PER DWG. |
12/30/2003 | SIGN ELECTRIC | RHOLLAND | Approved | IVRS - Inspection 0999*/ 1) PROPERLY SUPPORT AND INSTALL RACEWAY 348 2) FITTING TO BE FOR WEATHER PROOF USE 3) NM CABLE NOT ALLOWED IN A RACEWAY SYSTEM 4) PROTECT PRIMARY CONDUCTORS TO THE SWITCH 5) SIGN BODY TO BE WEATHER PROOF 6) VERIFY LISTING FOR WET LOCATION OF ELECTRO BIT SPLICES 7) NO PLANS OR PERMIT ON SITE |
01/06/2005 | PERMIT FINALED | LJACKSON | Approved |