Permit: T03ME00561
Permit Details
Apply Date:
09/26/2003
Applicant:
ABLE REFRIGERATION
Description:
REPLACE:FURNACE (APA)
Contractors:
- ABLE REFRIGERATION
Outstanding Activity Conditions
Permit Number - T03ME00561
Permit Status: Expired
Permit Description: REPLACE:FURNACE (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/26/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T03ME00561
Permite Description: REPLACE:FURNACE (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2003 | MECHANICAL - FINAL | N/A | Partial Approval | IVRS - Inspection 0000*/ INCORRECT SIZE FLEX GAS LINE, FURN. INPUT RATING 110,000 BTHU, FLEX LINE 3/8 X 18" RATED 93,100 BTHU. CORRECT/RECALL. |