Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
3302 N TREAT CI
Address NEW:
3302 N TREAT CI
Apply Date:
07/14/2003
Applicant:
AZTEC AIR CONDITIONING INC *T
Description:
REPLACE:4TON A/C & FURNACE (APA)
Contractors:
  • AZTEC AIR CONDITIONING INC *T

Outstanding Activity Conditions

Permit Number - T03ME00384
Permit Status: Expired
Permit Description: REPLACE:4TON A/C & FURNACE (APA)
Total Outstanding Activity Conditions - 1
Date Name
07/14/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T03ME00384
Permite Description: REPLACE:4TON A/C & FURNACE (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
07/18/2003 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*/ 1) LEVEL CONDENSOR ? OUT OF PITCH 2) EXPOSED CONTROL WIRING. PROTECT FROM SUN AS NECESSARY 3) EXTEND FURNACE VENT PIPE TERMINATE ABOVE TOP OF EVAP. COOLER 4) FURNACE GAS PIPING, INCOMPLETE 5) CONDENSATE PUMP-OVERFLOW SAFETY ?? SWITCH NOT CONNECTED. CONDENSATE PUMP DRAIN LINE. DO NOT RUN 3/8 " CLEAR PLASTIC TUBING UP TO ROOF. RUN 3/8" COPPER UP AND OUT OF ROOF