Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address NEW:
625 S SANTA ANA PL
Apply Date:
10/15/2003
Applicant:
CRAIG ZIMMERMAN
Description:
RELOCATE/UPGRADE:ELECTRIC TO 200 AMPS

Outstanding Activity Conditions

Permit Number - T03EL02039
Permit Status: Final
Permit Description: RELOCATE/UPGRADE:ELECTRIC TO 200 AMPS
Total Outstanding Activity Conditions - 1
Date Name
10/15/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T03EL02039
Permit Description: RELOCATE/UPGRADE:ELECTRIC TO 200 AMPS
Total Completed Inspections - 6
Date Description Inspector Results Comments
11/04/2003 ELECTRIC - TEMPORARY SERVICE JORTA Approved
11/05/2003 ELECTRIC - CABLE DROP JORTA Approved IVRS - Inspection 0000*SENT TO TEP ON 1105AM
11/05/2003 ELECTRIC - INTERMEDIATE JORTA Approved IVRS - Inspection 0000*/ 1) #4 CU. BARE WIRE ON WRONG SIDE OF ACORN CLAMP. TERMINATE INTO WEDGED AREA 2) WILL NEED TO SEE 2ND GROUND ROD ON FINAL 3) SUPPORT 2" CONDUIT AT ROOF TOP WITHIN 3 FEET OF L.B. CONDUIT 4) OK TO CLEAR TO TEP CABLE DROP AND TEMP POWER
11/05/2003 ELECTRIC - UNDERGROUND JORTA Approved IVRS - Inspection 0000*
02/26/2007 ELECTRIC - FINAL GDABBS Approved IVRS - Inspection :*
NOTE: NEW SERVICE IS UNDERGROUND FEED W/2 GROUND RODS.
02/27/2007 PERMIT FINALED BFLORES Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW