Permit: T03EL01960
Permit Details
Apply Date:
10/02/2003
Applicant:
CONNECT ELECTRIC *C
Description:
UPGRADE:ELECTRIC 200AMP (APA)
Contractors:
- CONNECT ELECTRIC *C
Outstanding Activity Conditions
Permit Number - T03EL01960
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC 200AMP (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/02/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T03EL01960
Permit Description: UPGRADE:ELECTRIC 200AMP (APA)
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2003 | ELECTRIC - FINAL | JORTA | Approved | IVRS - Inspection 0999*/1) NEED PERMANENT METAL ADDRESS TAG. 2) NO ACCESS FOR WIRE WITHDRAWL WITH L.R. CONDULATE IN INACCESSABLE UTILITY COVERED AREA. BRING L.R. DOWN INTO PREMISSES PANEL BOARD AREA. 3) 100 AMP. Q.P. BREAKER NOT ON LISTING TO BE USED. 4) PROPER SEALING FITTINGS TO BE USED WHERE APLICABLE. |
| 10/06/2003 | ELECTRIC - INTERMEDIATE | JORTA | Approved | IVRS - Inspection 0000* |
| 10/06/2003 | ELECTRIC - UNDERGROUND | JORTA | Approved | IVRS - Inspection 0000* |
| 01/21/2004 | PERMIT FINALED | RHOLLAND | Approved |